Features of Loop Calibrator
The fast, one-handed tool for loop checks. Just click to calibrate.
This feature-rich solution combines the best features push-button and knob-base loop calibrator and offers:
Large display and simple, quick-click interface for easy one-handed operation.
mA accuracy of 0.025%, superior to other loop calibrators in this price range.
Simultaneous mA and % readout for quick, easy interpretation of readings.
1 µA resolution for mA source, simulate and measure.
Selectable slow ramp, fast ramp, and step ramp to provide smooth outputs for valve slewing and loop functional tests.
0-100% ‘span check’ for fast confirmation of zero and span.
24 volt internal loop supply, so you can power and read a transmitter at the same time without carrying a DMM.
HART ™ mode connects 250 Ω resistor in series with 24 V loop for compatibility with HART communicators.
Measures V dc to 28 V.
Single 9V battery that is easily changed without braking calibration seal
Push button 25% steps for fast, easy linearity checks.
0 - 20 mA or 4 - 20 mA default start up modes.
Innovative output adjustment dial with 1 µA and 100 resolution.
Specifications of Loop Calibrator
Current Measurement
|
Range:
|
0 to 24 mA
| ||
Resolution:
|
0.001 mA
| |||
Accuracy:
|
0.025% Rdg + 2 LSD
| |||
Current Sourcing
|
Range:
|
0 to 20 mA or 4 to 20 mA
| ||
Accuracy:
|
0.025% Rdg + 2 LSD
| |||
Drive Capability:
|
1200 Ω; 950 Ω at 20 mA in HART mode
| |||
Current Simulation
|
Range:
|
0 to 20 mA or 4 to 20 mA
| ||
Accuracy:
|
0.025% Rdg + 2 LSD
| |||
Ext. loop voltage requirement:
|
12-30 V
| |||
Loop Power
|
While measuring mA, 24 V
| |||
Voltage measurement
|
Range:
|
0 to 28 V DC
| ||
Resolution:
|
1 mV
| |||
Accuracy:
|
0.025% Rdg + 2 LSD
| |||
Environmental Specifications
| ||||
Operating Temperature
|
-10ºC to 55ºC
| |||
Storage Temperature
|
-30ºC to 60ºC
| |||
Humidity (Without Condensation)
|
0 to 90% (0ºC to 35ºC); 0 to 70% (35ºC to 55ºC)
| |||
Temperature Coefficient
|
-10ºC to 18ºC, 28ºC to 55ºC, ±.005% of range per ºC
|
没有评论: